Ametek Over Temperature Protection Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para Sensores Ametek Over Temperature Protection. AMETEK Over Temperature Protection User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 2
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
Motogard
Series 150
CONNECTIONS
Power Connections:
Connect 120/240 VAC to input terminals 1 and 2.
Sensor Connections:
1. Connect one lead of each thermistor to Terminal 3.
2. Connect other lead of each Thermistors in series through to Terminal 4.
3. Maximum number of Thermistors in series: Three (3)
Output Load Connections:
1. Terminals 5, 6 and 7 comprise a set of “form C” contacts with terminal 6 common.
Terminal 5 is the open side. Terminal 7 is the closed side.
2. Be sure power is never applied directly across contacts but always in series with a load.
3. Maximum allowable load - 5 amps at 115 VAC
4. The closed output of the Motogard Over Temperature Protection System has been
specifically designed to operate directly in series with most main line contactors. If a small
interposing relay must be used, the sealed burden should be greater than 10VA.
5. The open output of the Series “150” controller can be used for trip indication.
See opposite side for possible wiring option.
Vista de página 0
1 2

Resumo do Conteúdo

Página 1 - Motogard

MotogardSeries 150CONNECTIONSPower Connections:Connect 120/240 VAC to input terminals 1 and 2.Sensor Connections:1. Connect one lead of each thermisto

Página 2 - 01/02.Z92

931150.I1R1 01/02.Z925C1080 N. Crooks Road ! Clawson, MI 48017800-635-0289 ! 248-435-0700 ! Fax 248-435-8120www.ametekapt.com ! www.ametek.com

Comentários a estes Manuais

Sem comentários